PresentationThe Altivar 212 is a variable speed drive for 3-phase asynchronous motors from 0.75 kW to 75 kW. It is specifically intended for the most commonly encountered fluid management applications in tertiary sectorbuildings (HVAC): heating, ventilation, air conditioning and pumping.Due to its eco-energy based design, energy savings of up to 70% can be achieved compared to a traditional control system. Characteristics: - Altivar 212 covers motor powers between 0.75 kW and 75 kW on the following supplies:
•200…240V 3-phase, from 0.75 kW to 30 kW, IP 21 •380…480V 3-phase, from 0.75 kW to 75 kW, IP 21 •380…480V 3-phase, from 0.75 kW to 75 kW, UL Type 12/IP 55 - Speed range: 1:50
- Transient overtorque: 110% - 60 s.
- Integrated EMC filters, categories C1 to C3 depending on model
- Communication bus most commonly used on the market integrated: Modbus, METASYS N2®, APOGEE FLN P1® and BACnet®. Optional: LonWorks
- Complies to international standards and certifications: UL, CSA, C-Tick and NOM
- Antiharmonic technology enables a THDI < 30% to be achieved
BenefitsCentred on Centralised Technical Management - Instant viewing of the energy consumption.
- Detection of failures for quick intervention: belt breakage, pump running dry, phase failure, supply fault, etc.
- Preventative maintenance for reducing costs and optimising the equipment: fault alert, operating time, etc.
- Connection to building supervision network using embedded protocols.
Centred on user-friendliness - Tools for installing, parametering and viewing the installation (remote graphic terminal in 6 languages, Multi-Loader, Bluetooth and SoMove Mobile).
- Compact size.
- Simple maintenance.
Centred on protection - Continuity of service assured.
- Dedicated “Building” series functions (fire mode, register monitoring, mechanical protection function, etc.
- Integrated EMC filter, antiharmonic technology (THDI ˜ 30%).
ApplicationsVentilation: - Less noise pollution (airdraulic noise, motor noise, etc.).
- Detection of transmission component breakage.
- Smoke extraction: forced start with fault inhibition.
- Automatic restart.
- Allows register management.
Heating and Air conditioning: - Optimise control in fluid processing.
- Use of PID controller (temperature, flow rate, pressure, etc.).
- Adjustable flow rates for better energy management.
- Suppression of mechanical resonance.
Pumping: - Detection of underload/overload, pump running dry.
- Multi-motor configuration.
- Limitation of operating time at low speed.
- Sleep/Wake function.
- Pressure surge suppression for prolonging the life of the installation.
Main Range of product | Altivar 212
| Product or component type | Variable speed drive
| Device short name | ATV212
| Product destination | Asynchronous motors
| Product specific application | Pumps and fans in HVAC
| Assembly style | With heat sink
| Network number of phases | 3 phases
| Motor power kW | 30 kW
| Motor power hp | 40 hp
| Power supply voltage | 380...480 V (- 15...10 %)
| Power supply voltage limits | 323...528 V
| Supply frequency | 50...60 Hz (- 5...5 %)
| Network frequency | 47.5...63 Hz
| EMC filter | Class C2 EMC filter integrated
| Line current | 56.7 A for 380 V 44.7 A for 480 V
|
Complementary Apparent power | 44.6 kVA for 380 V
| Prospective line Isc | 22 kA
| Continuous output current | 58.5 A at 380/460 V
| Maximum transient current | 64.4 A for 60 s
| Speed drive output frequency | 0.5...200 Hz
| Nominal switching frequency | 8 kHz
| Switching frequency | 8...16 kHz with derating factor 6...16 kHz adjustable
| Speed range | 1...10
| Speed accuracy | +/- 10 % of nominal slip for 0.2 Tn to Tn torque variation
| Torque accuracy | +/- 15 %
| Transient overtorque | 120 % of nominal motor torque, +/- 10 % for 60 s
| Asynchronous motor control profile | Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
| Regulation loop | Adjustable PI regulator
| Motor slip compensation | Adjustable Automatic whatever the load Not available in voltage/frequency ratio motor control
| Local signalling | 1 LED - red - DC bus energized
| Output voltage | <= power supply voltage
| Isolation | Electrical between power and control
| Type of cable for external connection | UL 508 cable with UL Type 1 kit: 3 wire(s) - 40 °C, copper 75 °C / PVC IEC cable without mounting kit: 1 wire(s) - 45 °C, copper 70 °C / PVC IEC cable without mounting kit: 1 wire(s) - 45 °C, copper 90 °C / XLPE/EPR
| Electrical connection | Terminal 50 mm² / AWG 1/0 (L1/R, L2/S, L3/T) Terminal 2.5 mm² / AWG 14 (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
| Tightening torque | 24 N.m - 212 lb.in (L1/R, L2/S, L3/T) 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
| Supply | Internal supply: 24 V (21...27 V) DC - <= 200 A with overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC, +/- 5 % - <= 10 A with overload and short-circuit protection
| Analogue input number | 2
| Analogue input type | Configurable voltage: (VIB) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 10 bits Switch-configurable current: (VIA) 0...20 mA - 250 Ohm - resolution: 10 bits Switch-configurable voltage: (VIA) 0...10 V DC - 24 V max - 30000 Ohm - resolution: 10 bits Configurable PTC probe: (VIB) 0...6 probes - 1500 Ohm
| Sampling duration | 22 ms +/- 0.5 ms (VIB) - analog input(s) 3.5 ms +/- 0.5 ms (VIA) - analog input(s) 2 ms +/- 0.5 ms (RES) - discrete input(s) 2 ms +/- 0.5 ms (R) - discrete input(s) 2 ms +/- 0.5 ms (F) - discrete input(s)
| Response time | 7 ms +/- 0.5 ms (RY, RC) - discrete output(s) 7 ms +/- 0.5 ms (FLB, FLC) - discrete output(s) 7 ms +/- 0.5 ms (FLA, FLC) - discrete output(s) 2 ms +/- 0.5 ms (FM) - analog output(s)
| Accuracy | +/- 1 % (FM) for a temperature variation 60 °C +/- 0.6 % (VIB) for a temperature variation 60 °C +/- 0.6 % (VIA) for a temperature variation 60 °C
| Linearity error | +/- 0.2 % for output (FM) +/- 0.15 % of maximum value for input (VIB) +/- 0.15 % of maximum value for input (VIA)
| Analogue output number | 1
| Analogue output type | Switch-configurable current: (FM) 0...20 mA - 970 Ohm - resolution: 10 bits Switch-configurable voltage: (FM) 0...10 V DC - 7620 Ohm - resolution: 10 bits
| Discrete output number | 2
| Discrete output type | Configurable relay logic: (RY, RC) NO - 100000 cycles Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (FLA, FLC) NO - 100000 cycles
| Minimum switching current | 3 mA at 24 V DC (configurable relay logic)
| Maximum switching current | 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
| Discrete input type | Programmable (RES) 24 V DC, with level 1 PLC - 4700 Ohm Programmable (R) 24 V DC, with level 1 PLC - 4700 Ohm Programmable (F) 24 V DC, with level 1 PLC - 4700 Ohm
| Discrete input logic | Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
| Acceleration and deceleration ramps | Automatic based on the load Linear adjustable separately from 0.01 to 3200 s
| Braking to standstill | By DC injection
| Protection type | With PTC probes for motor Motor phase break for motor Thermal protection for motor Against input phase loss for drive Line supply undervoltage for drive Line supply overvoltage and undervoltage for drive Against exceeding limit speed for drive Break on the control circuit for drive Overvoltages on the DC bus for drive Overcurrent between output phases and earth for drive Input phase breaks for drive Short-circuit between motor phases for drive Thermal power stage for drive Overheating protection for drive
| Dielectric strength | 5092 V DC between control and power terminals 3535 V DC between earth and power terminals
| Insulation resistance | >= 1 MOhm at 500 V DC for 1 minute
| Frequency resolution | 0.024/50 Hz for analog input 0.1 Hz for display unit
| Communication port protocol | APOGEE FLN BACnet LonWorks METASYS N2 Modbus
| Connector type | 1 RJ45 1 open style
| Physical interface | 2-wire RS 485
| Transmission frame | RTU
| Transmission rate | 9600 bps or 19200 bps
| Data format | 8 bits, 1 stop, odd even or no configurable parity
| Type of polarization | No impedance
| Number of addresses | 1...247
| Communication service | Monitoring inhibitable Read device identification (43) Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s Write multiple registers (16) 2 words maximum Write single register (06)
| Option card | Communication card for LonWorks
| Operating position | Vertical +/- 10 degree
| Width | 240 mm
| Height | 420 mm
| Depth | 214 mm
| Product weight | 26.4 kg
| Power dissipation in W | 847 W
| Fan flow rate | 290 m3/h
|
Environment Electromagnetic compatibility | Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
| Pollution degree | 3 IEC 61800-5-1
| IP degree of protection | IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1
| Vibration resistance | 1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-8 1.5 mm (f = 3...13 Hz) conforming to EN/IEC 60068-2-6
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27
| Environmental characteristic | Classes 3S2 conforming to IEC 60721-3-3 Classes 3C1 conforming to IEC 60721-3-3
| Noise level | 59.9 dB conforming to 86/188/EEC
| Operating altitude | 1000...3000 m (limited to 2000 m for the Corner Grounded distribution network) with current derating 1 % per 100 m <= 1000 m without derating
| Relative humidity | 5...95 % without dripping water conforming to IEC 60068-2-3 5...95 % without condensation conforming to IEC 60068-2-3
| Ambient air temperature for operation | > 40...50 °C with derating factor -10...40 °C without derating
| Ambient air temperature for storage | -25...70 °C
| Standards | EN 55011 class A group 1 EN 61800-3 EN 61800-3 category C2 EN 61800-3 category C3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 EN 61800-5-1 IEC 61800-3 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 UL Type 1
| Product certifications | CSA C-Tick NOM 117 UL
| Marking | CE
|
Offer Sustainability
|
|
|
|
|
|
|