|
|
|
|
Presentation3-phases 200/240 V - 380/480 V - 500/690 V - UL Type 1/IP20 from 0.75 to 800 kW.
- UL Type 12/IP54 from 0.75 to 90 kW.
- Speed range: 1:100 in open loop mode.
- Overload: 110% ... 120% - 60 s.
- Graphic keypad: plain text, navigation button, "Simply Start" menu to start immediately and profit at once from the full performance of Altivar 61. v Integrated EMC filters class A or B.
- Energy saving law, Quadratic motor control law.
- Conformity to the international Standards and Certifications: CE, UL, CSA, C-Tick.
- Modbus and CANopen integrated.
- Communication cards for industry: Ethernet, FIPIO, Modus Plus, DeviceNet, Interbus-S, Unitelway and for building LonWorks, BACnet, METASYS N2 and Apogee FLN.
- Input/output extension cards
- Multipump programmable cards: ATV38 compatibility and new applications.
- More than 150 functions available.
- Protection of motor and drive:
- Safety function: "Power Removal", ATEX.
- SoMove software for configuring on PC and transferring the configuration via Bluetooth® or using a cable
- SoMove Mobile software for modifying or sending a configuration remotely via mobile phone
ApplicationsRange dedicated to pump and fan applications for the industry and building markets: exceptional performances, advanced functionalities. High performance variable torque applications: - Fan: Safety with forced function (fault inhibition, selection of operating direction and the reference speed).
- Multipump: With the programmable card multipump, Altivar 61 offers you flexibility, user-friendliness and adaptability for management of several pumps.
- Pumps: Essential functions for your installation protection under load, overload and fluid absence detection.
Main Range of product | Altivar 61
| Product or component type | Variable speed drive
| Product specific application | Pumping and ventilation machine
| Component name | ATV61
| Motor power kW | 250 kW 3 phases at 690 V 200 kW 3 phases at 500 V
| Motor power hp | 250 hp 3 phases at 575 V
| Power supply voltage | 500...690 V (- 15...10 %)
| Supply number of phases | 3 phases
| Line current | 277 A for 500 V 3 phases 200 kW / 250 hp 257 A for 690 V 3 phases 200 kW / 250 hp 250 A for 600 V 3 phases 200 kW / 250 hp
| EMC filter | Level 3 EMC filter
| Assembly style | With heat sink
| Maximum prospective line Isc | 35 kA 3 phases
| Maximum transient current | 374.4 A for 60 s 3 phases
| Nominal switching frequency | 2.5 kHz
| Switching frequency | 2.5...4.9 kHz with derating factor 2.5...4.9 kHz adjustable
| Asynchronous motor control | Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f
| Synchronous motor control profile | Vector control without sensor, standard
| Communication port protocol | CANopen Modbus
| Type of polarization | No impedance for Modbus
| Option card | Profibus DP V1 communication card Profibus DP communication card Multi-pump card Modbus/Uni-Telway communication card Modbus TCP communication card Modbus Plus communication card METASYS N2 communication card LonWorks communication card Interbus-S communication card I/O extension card Fipio communication card Ethernet/IP communication card DeviceNet communication card Controller inside programmable card CC-Link communication card BACnet communication card APOGEE FLN communication card
|
Complementary Product destination | Asynchronous motors Synchronous motors
| Power supply voltage limits | 425...759 V
| Power supply frequency | 50...60 Hz (- 5...5 %)
| Power supply frequency limits | 47.5...63 Hz
| Continuous output current | 312 A at 2.5 kHz, 500 V 3 phases 290 A at 2.5 kHz, 690 V 3 phases 242 A at 2.5 kHz, 575 V 3 phases
| Speed drive output frequency | 0.1...500 Hz
| Speed range | 1...100 in open-loop mode, without speed feedback
| Speed accuracy | +/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedback
| Torque accuracy | +/- 15 % in open-loop mode, without speed feedback
| Transient overtorque | 130 % of nominal motor torque, +/- 10 % for 60 s
| Braking torque | 30 % without braking resistor <= 125 % with braking resistor
| Regulation loop | Frequency PI regulator
| Motor slip compensation | Adjustable Automatic whatever the load Can be suppressed Not available in voltage/frequency ratio (2 or 5 points)
| Diagnostic | 1 LED red presence of drive voltage
| Output voltage | <= power supply voltage
| Electrical isolation | Between power and control terminals
| Type of cable for mounting in an enclosure | Without mounting kit : 1-strand IEC cable at 45 °C, copper 90 °C XLPE/EPR Without mounting kit : 1-strand IEC cable at 45 °C, copper 70 °C PVC With UL Type 1 kit : 3-strand UL 508 cable at 40 °C, copper 75 °C PVC With an IP21 or an IP31 kit : 3-strand IEC cable at 40 °C, copper 70 °C PVC
| Electrical connection | PC/-, PA/+ terminal 4 x 185 mm² / 3 x 350 kcmil L1/R, L2/S, L3/T, U/T1, V/T2, W/T3 terminal 4 x 185 mm² / 3 x 350 kcmil AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR terminal 2.5 mm² / AWG 14
| Tightening torque | PC/-, PA/+ 41 N.m / 360 lb.in L1/R, L2/S, L3/T, U/T1, V/T2, W/T3 41 N.m / 360 lb.in AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR 0.6 N.m
| Supply | Internal supply 24 V DC (21...27 V), <= 200 mA for overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <= 10 mA for overload and short-circuit protection External supply 24 V DC (19...30 V), 30 W
| Analogue input number | 2
| Analogue input type | AI2 software-configurable voltage 0...10 V DC, input voltage 24 V max, impedance 30000 Ohm, resolution 11 bits AI2 software-configurable current 0...20 mA, impedance 242 Ohm, resolution 11 bits AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max, resolution 11 bits + sign
| Sampling time | Discrete input LI6 (if configured as logic input) 2 ms, +/- 0.5 ms Discrete input LI1...LI5 2 ms, +/- 0.5 ms Analog output AO1 2 ms, +/- 0.5 ms Analog input Al2 2 ms, +/- 0.5 ms Analog input AI1-/Al1+ 2 ms, +/- 0.5 ms
| Absolute accuracy precision | AO1 +/- 1 % for a temperature variation 60 °C AI2 +/- 0.6 % for a temperature variation 60 °C AI1-/Al1+ +/- 0.6 % for a temperature variation 60 °C
| Linearity error | AO1 +/- 0.2 % AI2 +/- 0.15 % of maximum value AI1-/Al1+ +/- 0.15 % of maximum value
| Analogue output number | 1
| Analogue output type | AO1 software-configurable logic output 10 V, <= 20 mA AO1 software-configurable voltage, analogue output range 0...10 V DC, impedance 470 Ohm, resolution 10 bits AO1 software-configurable current, analogue output range 0...20 mA, impedance 500 Ohm, resolution 10 bits
| Discrete output number | 2
| Discrete output type | (R2A, R2B) configurable relay logic NO, electrical durability 100000 cycles (R1A, R1B, R1C) configurable relay logic NO/NC, electrical durability 100000 cycles
| Maximum response time | R2A, R2B <= 7 ms, tolerance +/- 0.5 ms R1A, R1B, R1C <= 7 ms, tolerance +/- 0.5 ms <= 100 ms in STO (Safe Torque Off)
| Minimum switching current | Configurable relay logic 3 mA at 24 V DC
| Maximum switching current | R1, R2 on resistive load, 5 A at 30 V DC, cos phi = 1, L/R = 0 ms R1, R2 on resistive load, 5 A at 250 V AC, cos phi = 1, L/R = 0 ms R1, R2 on inductive load, 2 A at 30 V DC, cos phi = 0.4, L/R = 7 ms R1, R2 on inductive load, 2 A at 250 V AC, cos phi = 0.4, L/R = 7 ms
| Discrete input number | 7
| Discrete input type | (PWR) safety input, 24 V DC, voltage limits <= 30 V, impedance 1500 Ohm (LI6) switch-configurable PTC probe, 0...6, impedance 1500 Ohm (LI6) switch-configurable, 24 V DC, voltage limits <= 30 V, with level 1 PLC, impedance 3500 Ohm (LI1...LI5) programmable, 24 V DC, voltage limits <= 30 V, with level 1 PLC, impedance 3500 Ohm
| Discrete input logic | LI6 (if configured as logic input) positive logic (source), < 5 V (state 0), > 11 V (state 1) LI6 (if configured as logic input) negative logic (sink), > 16 V (state 0), < 10 V (state 1) LI1...LI5 positive logic (source), < 5 V (state 0), > 11 V (state 1) LI1...LI5 negative logic (sink), > 16 V (state 0), < 10 V (state 1)
| Acceleration and deceleration ramps | Automatic adaptation of ramp if braking capacity exceeded, by using resistor Linear adjustable separately from 0.01 to 9000 s S, U or customized
| Braking to standstill | By DC injection
| Protection type | Motor thermal protection Motor power removal Motor motor phase break Drive thermal protection Drive short-circuit between motor phases Drive power removal Drive overvoltages on the DC bus Drive overheating protection Drive overcurrent between output phases and earth Drive line supply undervoltage Drive line supply overvoltage Drive input phase breaks Drive break on the control circuit Drive against input phase loss Drive against exceeding limit speed
| Insulation resistance | > 1 mOhm at 500 V DC for 1 minute to earth
| Frequency resolution | Display unit 0.1 Hz Analog input 0.024/50 Hz
| Type of connector | Male SUB-D 9 on RJ45 for CANopen 1 RJ45 for Modbus on terminal 1 RJ45 for Modbus on front face
| Physical interface | 2-wire RS 485 for Modbus
| Transmission frame | RTU for Modbus
| Transmission rate | 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen 9600 bps, 19200 bps for Modbus on front face 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
| Data format | 8 bits, odd even or no configurable parity for Modbus on terminal 8 bits, 1 stop, even parity for Modbus on front face
| Number of addresses | 1...247 for Modbus 1...127 for CANopen
| Method of access | Slave for CANopen
| Marking | CE
| Operating position | Vertical +/- 10 degree
| Product weight | 181 kg
| Width | 595 mm
| Height | 1190 mm
| Depth | 377 mm
|
Environment Noise level | 77 dB conforming to 86/188/EEC
| Dielectric strength | 5345 V DC between control and power terminals 3110 V DC between earth and power terminals
| Electromagnetic compatibility | Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 level 3 Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4 Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3
| Standards | EN 55011 class A group 2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 60721-3-3 class 3C2 UL Type 1
| Product certifications | CSA C-Tick DNV GOST NOM 117 UL
| Pollution degree | 3 conforming to UL 840 3 conforming to EN/IEC 61800-5-1
| Degree of proctection | IP30 on the front panel conforming to EN/IEC 61800-5-1 IP30 on the front panel conforming to EN/IEC 60529 IP30 on side parts conforming to EN/IEC 61800-5-1 IP30 on side parts conforming to EN/IEC 60529 IP00 conforming to EN/IEC 61800-5-1 IP00 conforming to EN/IEC 60529 IP54 on lower part conforming to EN/IEC 61800-5-1 IP54 on lower part conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529
| Vibration resistance | 1.5 mm peak to peak (f = 3...10 Hz) conforming to EN/IEC 60068-2-6 0.6 gn (f = 10...200 Hz) conforming to EN/IEC 60068-2-6
| Shock resistance | 4 gn for 11 ms conforming to EN/IEC 60068-2-27
| Relative humidity | 5...95 % without dripping water conforming to IEC 60068-2-3 5...95 % without condensation conforming to IEC 60068-2-3
| Ambient air temperature for operation | 50...60 °C with derating factor -10...50 °C without derating
| Ambient air temperature for storage | -25...70 °C
| Operating altitude | 1000...2260 m with current derating 1 % per 100 m <= 1000 m without derating
|
Offer Sustainability
|
|
|
|
|
|
|