Device short name |
XW+ 5548 NA |
Inverter AC output |
|
Output power (continuous) at 25°C |
5500 W |
Overload 30 min / 60 sec at 25°C |
7000 W / 9500 W |
Output power (continuous) at 40°C |
4500 W |
Maximum output current 60 seconds (rms) |
82 A (120 V); 41 A (240 V) |
Output frequency (selectable) |
50 / 60 Hz |
Output voltage |
L-N: 120 V +/- 3%; L-L: 240 V +/- 3% |
Total harmonic distortion (THD) at rated power |
< 5% |
Idle consumption search mode |
< 8 W |
Input DC voltage range |
42 to 60 V (48 V Nominal) |
Maximum input DC current |
150 A |
Charger DC output |
|
Maximum output charge current |
110 A |
Output voltage range |
40 - 64 V (48 V Nominal) |
Charge control |
Three stage, two stage, boost, custom |
Charge temperature compensation |
Battery temperature sensor included |
Power factor corrected charging |
0.98 |
Compatible battery types |
Flooded (default), Gel, AGM, LiON, custom* Flooded (default),
Gel, AGM,LiON, custom* |
Batter bank range (scaled to PV array size) |
440 - 10000 Ah |
AC input |
|
AC 1 (grid) input current (selectable limit) |
3 - 60 A (60 A default) |
AC 2 (generator) input current (selectable
limit) |
3 - 60 A (60 A default) |
Automatic transfer relay rating / typical transfer
time |
60 A / 8 ms |
AC input voltage limits
(bypass/charge mode) |
L-N: 78 - 140 V (120 V
nominal); L-L: 160 - 270 V (240 V nominal) |
AC input frequency range (bypass/charge mode) |
55 - 65 Hz (default); 52 - 68 Hz (allowable) |
AC grid-tie output |
|
Grid sell current range on AC1(selectable
limit) |
0 to 40 A (120 V) / 0 to 20 A (240 V) |
Grid sell voltage range on
AC1
(auto adjusts entering sell mode) |
L-N:105.5 to 132 +/-
1.5 V; L-L: 211 to 264 +/- 3.0 V |
Grid sell frequency range on
AC1 (auto adjust entering sell mode) |
59.4 to 60.4 +/- 0.05 Hz |
Efficiency |
|
Peak |
95.70% |
CEC weighted efficiency |
93.00% |
General specifications |
|
Part number |
865-5548-01 |
Product / shipping weight |
53.5 kg (118.0 lb) / 75.0 kg (165.0 lb) |
Product dimensions (H x W x D) |
58 x 41 x 23 cm (23 x 16 x 9 in) |
Shipping dimensions (H x W x D) |
71.1 x 57.2 x 39.4 cm (28.0 x 22.5 x 15.5 in) |
IP degree of protection |
NEMA Type 1 Indoor |
Operating air temperature range |
25°C to 70°C (-13°F to 158°F) (power derated above 25°C (77°F) |
Warranty (Depending on the country of
installation) |
2 or 5 years |
Features |
|
System monitoring and network communications |
Available |
Intelligent features |
Grid sell, peak load shave, generator support, prioritized
consumption of battery or external DC energy |
Auxiliary port |
0 to 12 V, maximum 250 mA DC output, selectable triggers |
Off-grid AC coupling |
Frequency control |
Multi-unit operation |
Single and split phase: up to four units in parallel, three
phase: up to 12 units in multi-cluster configuration with external AC
contractor |
Regulatory approval |
|
Safety |
UL1741, CSA 107.1 |
EMC directive |
FCC and Industry Canada Class B |
Interconnect |
IEEE 1547 and CSA 107.1 |